How do you test an AC contactor coil?

Here’s how you can test an AC contactor coil to see if it’s functioning properly:

Safety Precautions:

  • Before attempting any electrical work, always ensure the power is off to the AC unit. Turn off the circuit breaker controlling the AC and verify there’s no power using a voltage tester.
  • Never touch electrical components while the power is on, as this can lead to serious injury or even death.

Tools Required:

  • Multimeter: A multimeter is a versatile tool that can measure voltage, resistance, and current. You’ll need it to test the resistance of the contactor coil.
  • Screwdriver: A screwdriver is required to access the contactor coil by removing the wires connected to it.

Testing Procedure:

  1. Power Off and Access the Contactor:

    • Ensure the AC unit is completely off and power is disconnected.
    • Locate the contactor within the AC unit’s electrical panel. It’s a box-shaped component with wires connected to it and should be labelled accordingly.
  2. Disconnect the Coil Wires:

    • Use the screwdriver to carefully detach the wires connected to the contactor coil. Remember the location of each wire for proper reconnection later.
  3. Set Multimeter to Ohms Mode:

    • Turn on your multimeter and set it to the ohms (Ω) mode for measuring resistance.
  4. Test the Coil Resistance:

    • Touch one multimeter probe to each terminal of the disconnected contactor coil.
    • The multimeter should display a reading between a specified range, typically within 10 to 100 ohms for most contactor coils.
  5. Interpreting the Results:

    • Normal Reading: If the multimeter displays a reading within the specified range (e.g., 10-100 ohms), it suggests the contactor coil is likely functioning properly.
    • Open Coil: If the multimeter displays an “OL” (overload) or infinity (∞) symbol, it indicates an open circuit within the coil, meaning the coil is likely faulty and needs replacement.
    • Shorted Coil: If the multimeter displays a reading very close to zero (near short circuit), it suggests a possible short circuit within the coil, also indicating a potential malfunction requiring replacement.
  6. Reconnect the Wires:

    • Once testing is complete, carefully reconnect the wires to the contactor coil terminals, ensuring they are secured properly in their original positions.

Additional Considerations:

  • Consult the Manufacturer’s Specifications: If you’re unsure about the expected resistance range for your specific contactor model, refer to the manufacturer’s manual or specifications for the exact values.
  • Visual Inspection: While the resistance test is a good indicator, you can also do a visual inspection of the contactor coil for any signs of physical damage like burn marks or melting, which could also suggest a malfunction.
  • Seek Help from a Qualified Technician: If you’re uncomfortable with electrical work or unsure about the test results, it’s always best to consult a qualified HVAC technician for diagnosis and potential replacement of the contactor coil if necessary.

Remember, safety is paramount when dealing with electrical components. If you’re not confident performing these steps yourself, it’s advisable to seek professional help from a qualified electrician or HVAC technician.