SITC of Air-Cooled Chiller
(Supply, Installation, Testing & Commissioning)
An air-cooled chiller is a self-contained cooling system widely used in commercial buildings, hospitals, hotels, IT parks, and industrial facilities, especially where water availability or cooling towers are a constraint.
SITC ensures the chiller plant is delivered end-to-end—from approved equipment supply to a fully operational, performance-verified system.
1️⃣ Supply (S)
Procurement and delivery of consultant-approved equipment and accessories:
-
Air-cooled chiller(s) (scroll/screw, inverter as specified)
-
Primary/secondary chilled water pumps
-
Buffer tank (if specified)
-
Piping, valves, strainers, expansion tank
-
Insulation & cladding
-
Electrical panels, controls & BMS points
Checks at Supply Stage
-
Capacity (TR), COP/IPLV, design ΔT
-
Ambient derating suitability
-
Noise level compliance
-
Accessories and spares as per BOQ
2️⃣ Installation (I)
Chiller Placement & Mounting
-
Installation on RCC plinth / rooftop steel structure
-
Adequate air clearances for condenser airflow
-
Vibration isolation (springs/rubber pads)
-
Proper drainage for condensate and rainwater
Air recirculation at condenser is a common performance killer—clearances matter.
Chilled Water Piping
-
Correct pipe sizing as per hydraulic design
-
Qualified welding / grooving practices
-
Hydrostatic pressure testing before insulation
-
Proper insulation with vapor barrier to prevent sweating
Pumps, Valves & Accessories
-
Pump alignment and rotation checks
-
Installation of:
-
Isolation valves
-
Balancing valves
-
Strainers
-
Air vents & drains
-
Electrical & Controls
-
Power cabling with proper earthing
-
Control wiring and interlocks
-
Integration with BMS / EMS
-
Phase sequence and protection checks
3️⃣ Testing (T)
Testing ensures the system is safe and ready to operate:
-
Hydrostatic testing of piping
-
System flushing and cleanliness verification
-
Electrical insulation & continuity tests
-
Pre-start checks for compressors, fans, pumps
-
Safety interlock testing (HP/LP, flow switches)
4️⃣ Commissioning (C)
Commissioning proves the system performs as designed:
-
Initial start-up as per manufacturer SOP
-
Water flow balancing across circuits
-
Verification of ΔT, capacity, and power consumption
-
Part-load and full-load performance checks
-
Noise and vibration measurements
-
BMS point-to-point testing
Joint witnessing with consultant/PMC is recommended.
Documentation & Handover
-
Test & commissioning reports
-
As-built drawings
-
O&M manuals
-
Warranty certificates
-
Operator training and SOPs
Applications
-
Commercial offices & malls
-
Hospitals & healthcare
-
Hotels & institutions
-
Data centers (edge/backup)
-
Industrial process cooling
Why SITC Matters for Air-Cooled Chillers
-
Single-point responsibility
-
Faster commissioning
-
Predictable performance
-
Lower lifecycle risk
In Simple Words
SITC of an air-cooled chiller means supplying, installing, testing, and commissioning a complete chiller plant that is ready for operation and meets design performance.